1. Introducere
This manual provides essential information for the proper installation, operation, and maintenance of the Apollo Valve 14-200 Series Bronze Safety Relief Valve. This high-capacity steam safety valve is designed to protect heating boiler systems by automatically relieving excess pressure. Adherence to the guidelines presented herein is crucial for ensuring the safety, longevity, and optimal performance of the valve.
The Apollo Valve 14-200 series is ASME safety rated for Section IV heating boilers, making it suitable for use with medium and large size commercial and industrial heating boilers.
2. Informații de siguranță
AVERTIZARE: Improper installation, operation, or maintenance of this safety relief valve can result in property damage, serious injury, or death. Always follow all local codes, regulations, and manufacturer instructions.
- Ensure the valve is installed by qualified personnel in accordance with all applicable codes and standards.
- Verify that the valve's set pressure (15 psi) is appropriate for the system it is protecting.
- Nu tamper with the factory-set pressure. Any adjustments must be performed by authorized personnel using proper calibration equipment.
- Ensure proper discharge piping is installed to safely vent steam or fluid away from personnel and equipment.
- Regularly inspect the valve for signs of damage, corrosion, or leakage.
- Always depressurize the system before attempting any maintenance or inspection.
3. Produs terminatview
The Apollo Valve 14-200 Series is a robust bronze safety relief valve designed for reliable overpressure protection in steam heating boiler systems. Its construction features a durable cast bronze body, a steel spring, and a PTFE-faced disc for a positive seal.

Un detaliat view of the Apollo Valve 14-200 Series Bronze Safety Relief Valve, showing its robust bronze body, threaded inlet and outlet connections, and the top-mounted lift lever mechanism. The product label is visible, indicating model and pressure specifications.
Caracteristici cheie:
- Relief Pressure: Preset to 15 psi for effective pressure release.
- Conexiune de intrare: 2-1/2" male NPT threaded inlet for secure connection.
- Conexiune priză: 2-1/2" female NPT outlet.
- Constructie: Cast bronze body and steel spring for excellent corrosion resistance.
- Etanșare: Flat seat with a PTFE-faced disc for a reliable, positive seal.
- Certificare: ASME safety rated for Section IV heating boilers.
- Conexiune de scurgere: Features a 3/8" NPT side tapping for drain connection.
- Temperatura de functionare: Suitable for operating temperatures up to 250 degrees F.
4. Configurare și instalare
Installation of the Apollo Valve 14-200 Series Safety Relief Valve should only be performed by a qualified and licensed professional in accordance with all local and national plumbing and boiler codes.
Pașii de instalare:
- Pregătirea sistemului: Ensure the boiler system is depressurized and cooled before beginning installation.
- Conexiune de intrare: Thread the 2-1/2" male NPT inlet of the valve into the designated female NPT connection on the boiler. Use appropriate thread sealant to ensure a leak-free connection. Do not overtighten.
- Conexiune priză: Connect suitable discharge piping to the 2-1/2" female NPT outlet of the valve. The discharge piping must be adequately sized, sloped for drainage, and routed to a safe discharge point where steam or hot water can be safely released without causing harm or damage. Avoid any restrictions or valves in the discharge line.
- Drain Connection (Optional): If required, connect a 3/8" NPT drain line to the side tapping for condensate drainage.
- Verificare finală: After installation, slowly repressurize the system and carefully inspect all connections for leaks.
5. Principii de funcționare
The Apollo Valve 14-200 Series Safety Relief Valve operates automatically to protect the boiler from overpressure conditions. It is a spring-loaded, direct-acting valve.
- Under normal operating conditions, the system pressure is below the valve's set pressure (15 psi), and the valve remains closed, maintaining system integrity.
- If the system pressure exceeds the 15 psi set point, the force exerted by the pressure on the valve's disc overcomes the spring force, causing the disc to lift and the valve to open.
- Excess steam or fluid is then discharged through the outlet, reducing the system pressure to a safe level.
- Once the system pressure drops below the reseating pressure, the spring force closes the valve, restoring normal operation.
- The valve also features a manual lift lever for periodic testing, which should be performed carefully and only when the system is at a safe operating pressure, to ensure the valve is not seized. Consult boiler operation guidelines for proper testing procedures.
6. Întreținere
Regular maintenance is essential to ensure the continued reliability and safety of your Apollo safety relief valve. All maintenance should be performed by qualified personnel.
Program de întreținere:
- Inspecție anuală: Visually inspect the valve for any signs of external damage, corrosion, or leaks. Check the discharge piping for obstructions.
- Test operațional: Periodically test the valve by manually lifting the lever to ensure the disc moves freely and reseats properly. This should be done in accordance with boiler manufacturer recommendations and safety protocols.
- curatenie: If the valve shows signs of weeping or leakage, it may indicate debris on the seat. A gentle manual lift of the lever while the system is under pressure (if safe to do so per boiler manual) can sometimes clear minor debris. If leakage persists, the valve may need to be replaced.
- Înlocuire: Safety relief valves have a finite lifespan. It is recommended to replace the valve according to boiler manufacturer guidelines or if it fails any operational tests, shows signs of significant wear, or has discharged frequently.
7. Depanare
This section provides basic troubleshooting steps for common issues. For complex problems or if you are unsure, always consult a qualified professional.
| Problemă | Cauza posibila | Soluţie |
|---|---|---|
| Valve constantly weeping or leaking |
|
|
| Valve fails to open at set pressure |
|
|
| Valve opens too frequently |
|
|
8. Specificații
Detailed technical specifications for the Apollo Valve 14-200 Series Bronze Safety Relief Valve.
| Atribut | Valoare |
|---|---|
| Numărul de model | 1420608 |
| Marca | APOLLO |
| Tip supapă | Supapa de siguranță |
| Materialul corpului | Bronz |
| Material de primăvară | Oţel |
| Disc Material | PTFE-faced |
| Materialul scaunului | PTFE-coated EPDM O-ring |
| Setare Presiune | 15 psi |
| Tip de conectare la intrare | 2-1/2" Male NPT |
| Tip conexiune priză | 2-1/2" Female NPT |
| Conexiune de scurgere | 3/8" NPT Side Tapping |
| Temperatura maximă de funcționare | 250°F |
| Certificare ASME | Section IV Heating Boilers |
| Producător | Conbraco |
| UPC | 670750498381 |
| Dimensiuni pachet | 9.7 x 7.2 x 6.1 inci |
| Greutatea articolului | 12 lire sterline |
9. Garanție și asistență
For specific warranty information regarding the Apollo Valve 14-200 Series Safety Relief Valve, please refer to the documentation provided at the time of purchase or contact Apollo Valves directly. Warranty terms typically cover manufacturing defects under normal use and service.
For technical support, replacement parts, or further inquiries, please contact Apollo Valves customer service. Apollo Valves is a brand of Conbraco, a company founded in 1928 and headquartered in Matthews, NC, meeting international standard ISO/IEC 17025:2005.
Contact producator: Please visit the official Apollo Valves website or consult your local distributor for the most current contact information.