SmartGen HAT361 HAT361C

SmartGen HAT361 HAT361C Dual Power Automatic Switching Controller

Manual de utilizare

Model: HAT361, HAT361C | Brand: SmartGen

1. Introducere

The SmartGen HAT360 series dual power automatic transfer switch (ATS) controller, including models HAT361 and HAT361C, is designed with a microprocessor core for precise monitoring and control of dual power systems. It accurately measures two-way voltages, detects abnormalities (such as over/under voltage, over/under frequency, loss of phase, and reverse phase sequence), and intelligently manages the transfer between power sources. This controller integrates an LCD display and digital communication capabilities, providing a user-friendly interface for efficient power management.

The HAT361C model includes RS485 communication for remote control and monitoring via Modbus protocol.

2. Informații de siguranță

Vă rugăm să citiți și să înțelegeți toate instrucțiunile de siguranță înainte de instalare și utilizare. Nerespectarea acestor instrucțiuni poate duce la electrocutare, incendiu sau vătămări corporale grave.

  • Asigurați-vă că toate sursele de alimentare sunt deconectate înainte de a efectua orice instalare, cablare sau întreținere.
  • Numai personal calificat trebuie să instaleze și să întrețină acest echipament.
  • Verify all wiring connections are correct and secure according to the provided diagrams.
  • Do not operate the controller if it is damaged or malfunctioning.
  • Keep the controller away from moisture, extreme temperatures, and corrosive environments.
  • Asigurați o împământare adecvată pentru a preveni pericolele electrice.

3. Produs terminatview

The HAT361/HAT361C controllers are designed for dual power ATS applications, offering robust features for reliable power transfer.

3.1 Caracteristici și caracteristici

  • Configurable for 3P4W, 3P3W, 2P3W, or 1P2W AC systems.
  • Intelligent MCU-based monitoring and control.
  • S1/S2 master/slave configuration for auto transfer/restore and non-restore modes.
  • Supports Auto and Manual operation modes.
  • OFF mode disables breaker close/open functions.
  • System type settings for S1 Mains S2 Mains, S1 Gen S2 Mains.
  • Measures and displays 2-way 3-phase voltage, frequency, and alarm status.
  • Suitable for two-breaking, one-breaking, and no-breaking switches.
  • Includes switch re-closing function.
  • RS485 serial communication port (optional on HAT361C) for remote control, measuring, communication, and adjustment via Modbus protocol.
  • Overvoltage, subvoltage, overfrequency, underfrequency, loss of phase, and reverse phase sequence detection.
  • Adjustable thresholds for voltage and frequency abnormalities.
  • Manual test function for genset start/stop.
  • LED indicators for current ATS close status, power status, mode (manual/auto/OFF), and alarms.
  • Design izolat cu fir N cu 2 căi.

3.2 Aspectul panoului frontal

The front panel provides visual indicators and control buttons for easy operation.

SmartGen HAT361 Front Panel

Figure 1: SmartGen HAT361 Front Panel. Shows S1/S2 indicators, LOAD indicator, OFF button, Auto/Manual buttons, S1 Close/Open/S2 Close buttons, and the SmartGen display.

SmartGen HAT361C Front Panel

Figure 2: SmartGen HAT361C Front Panel. Similar layout to HAT361, indicating the 'C' model variant.

4. Configurare și instalare

Careful installation and wiring are crucial for the proper functioning of the ATS controller.

4.1 Controller Dimensions and Panel Cutout

The controller is designed for panel mounting. Ensure the panel cutout matches the specified dimensions.

MăsurareValoare
Dimensiunile carcasei132 mm x 102 mm x 49 mm
Decupaj panou132 mm x 102 mm

4.2 Rear Panel and Terminal Description

The rear panel houses all necessary connection terminals. Refer to the diagrams and table below for proper wiring.

SmartGen HAT361 Rear Panel Wiring Terminals

Figure 3: SmartGen HAT361 Rear Panel with Wiring Terminals. Shows inputs for S1/S2 AC voltage, GEN START, S1/S2 CLOSE INPUT, RS485, and AUX OUTPUT.

HAT361C Panel Diagram

Figure 4: HAT361C Panel Diagram. Detailed view of terminal numbering on the rear panel.

Nu.ArticolRemarcă
1A1AC 3 phase 4 wire voltage input of S1 (For single phase input, only connect A1,N1)
2B1
3C1
4N1
5A2AC 3 phase 4 wire voltage input of S2 (For single phase input, only connect A2,N2)
6B2
7C2
8N2
9NUATS supply power N (Provide supply power for ATS)
10NUATS supply power L (Capacity: 12A 250VAC)
11LOATS supply power L (NC for terminal 10 of HAT361)
12NU
13COMOutput common port
14S1 CLOSES1 close output (Capacity: 10A 250VAC)
15S2 CLOSES2 close output (Capacity: 10A 250VAC)
16S1 OPEN OUTPUTS1 open output (Capacity: 10A 250VAC)
17S2 OPEN OUTPUTS2 open output (Capacity: 10A 250VAC)
18GEN STARTGenset start output (Capacity: 7A 250VAC)
19COMInput common port
20FORCE OPENForced open input (Connect GND of input common port)
21COMInput common port
22S2 CLOSE INPUTS2 close input (Connect GND of input common port)
23COMInput common port
24S1 CLOSE INPUTS1 close input (Connect GND of input common port. Users need to connect this terminal to terminal 27 based on on-site network arrangement, used to connect with the 120Ω resistor inside the controller)
25TRRS485 matching resistor (120Ω impedance matching resistor inside the controller)
26TR
27B (-)Port de comunicație RS485
28A (+)
29COMPort comun
30INTRARE AUXAux. input (Connect GND of input common port)
31IEȘIRE AUXAux. output (Capacity: 10A 250VAC)
32

4.3 Diagrame de cablare tipice

Below are typical application wiring diagrams. Always consult local electrical codes and standards.

4.3.1 SGG-N/T Application Diagram

SGG-N/T Application Wiring Diagram

Figure 5: SGG-N/T Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for SGG-N/T type switches. Note: Suitable for HAT363 (No Breaking) controller model.

4.3.2 ATYS Application Diagram

ATYS Application Wiring Diagram

Figure 6: ATYS Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for ATYS type switches. Note: Suitable for HAT363 (One breaking) controller model.

4.3.3 PHETENG Application Diagram

PHETENG Application Wiring Diagram

Figure 7: PHETENG Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for PHETENG type switches. Note: Suitable for HAT363 (Two breakings) controller model.

4.3.4 Motor Type Application Diagram

Motor Type Application Wiring Diagram

Figure 8: Motor Type Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for Motor Type switches. Note: Suitable for HAT361/HAT363 (One breaking) controller model.

5. Funcționare

This section details the operational modes, key functions, and display information of the controller.

5.1 Indicator Display

The front panel LEDs provide immediate status feedback.

IndicatorDescriere
S1 Power IndicatorExtinguishes when S1 power blackout; Illuminates when S1 power is normal.
S1 Close IndicatorFlashes when S1 power is abnormal (over/under voltage, under/over frequency, loss of phase, reverse phase sequence); Illuminates when S1 is closed, otherwise, it extinguishes.
S2 Power IndicatorIlluminates when S2 power is normal; Extinguishes when S2 power blackout.
S2 Close IndicatorFlashes when S2 power is abnormal (over/under voltage, under/over frequency, loss of phase, reverse phase sequence); Illuminates when S2 is closed, otherwise, it extinguishes.
Indicator de alarmăIlluminates when there is an alarm.
OFF Mode IndicatorIlluminates in OFF mode, extinguishes in other modes.
Indicator mod automatIlluminates in Auto mode, extinguishes in other modes.
Indicator mod manualIlluminates in Manual mode, extinguishes in other modes.

5.2 Key Function Description

The controller features several keys for navigation and control.

PictogramăCheieDescrierea funcției
UpIn main interface, scrolls up the screen; In menu interface, moves cursor up or increases number.
JosIn main interface, scrolls down the screen; In menu interface, moves cursor down or reduces number.
*/okSet/Confirm/Lamp TestIn main interface, moves cursor and confirms settings. Long press tests lamps (all white screen, all LEDs illuminate, alarms reset).
OFFOFFEnters OFF mode, controller exits control.
AutoModul automatEnters Auto mode.
S1 CloseS1 CloseActive in manual mode; closes S1 outputs, S1 takes load.
DeschideDeschideActive in manual mode; load disconnects.
S2 CloseS2 CloseActive in manual mode; closes S2 outputs, S2 takes load.
ManualModul manualEnters Manual mode.

Ecran LCD 5.3

The LCD provides detailed information about the system status.

ConţinutDescriere
Afișaj interfață principală
S1 BlackoutS1 voltagStarea e
S2 BlackoutS2 voltagStarea e
DescărcareATS status
Genset WorkingStarea grupului electrogen
Modul manualLinia de stare
Volt
LL1S1 line voltage
LL2S2 line voltage
Volt
LN1S1 phase voltage
LN2S2 phase voltage
Frec
F1S1 frequency
F2S2 frequency
Secvența fazelor
P1S1 Phase Sequence
P2S2 Phase Sequence
S1 Failed to CloseInformații de alarmă

5.4 Moduri de operare

5.4.1 Mod manual

To enter Manual Mode, press the Manual key. The manual status indicator will illuminate. In this mode, you can manually control the S1 and S2 breakers:

  • S1 Close: If the load is open, S1 closes and supplies power to the load.
  • S2 Close: If the load is open, S2 closes and supplies power to the load.
  • Deschide: Disconnects the load from both power sources.

5.4.2 Mod automat

To enter Auto Mode, press the Auto key. The auto status indicator will illuminate. In Auto Mode, the controller automatically transfers the switch based on the status of S1 and S2 power, transfer priority, and auto transfer/restore settings to ensure continuous power supply to the load.

5.4.3 Auto Transfer/Restore Logic

The controller follows specific logic for automatic transfer and restoration. An example of 'S1 master' and 'S2 Mains S2 Gen' control logic is illustrated below:

Auto Transfer/Restore Flowchart

Figure 9: Auto Transfer/Restore Flowchart. Details the sequence of events for S1 Normal, S1 Abnormal, S2 Normal, and S2 Abnormal conditions, including delays and generator start signals.

5.4.4 Auto Transfer Non-Restore (Mutual Backup Active) Logic

This mode is used when both power sources act as mutual backups.

Auto Transfer Non-Restore Flowchart

Figure 10: Auto Transfer Non-Restore (Mutual Backup Active) Flowchart. Illustrates the logic for non-restorative transfer between S1 and S2.

6. Specificații

Detailed technical parameters for the HAT361/HAT361C controllers.

6.1 Parametrii tehnici

ArticoleCuprins
Vol. De operaretageAC supply, voltage range AC170-277V
Consumul de energie≤5W (Standby mode: ≤2W)
AC Voltage Intrare3P4W (L-N): AC170V~AC277V
3P3W (L-L): AC170V~AC277V
2P3W (L-N): AC170V~AC277V
1P2W (L-N): AC170V~AC277V
Vol. Evaluattagenominal: 380V
Frecvența nominalăRange: 50Hz/60Hz
PrecizieVoltage: ±2%, Frequency: ±0.1Hz
Închideți ieșirea releului10A AC250V volts free output
Ieșire releu auxiliar10A AC250V volts free output
Genset Crank Relay Output7A AC250V volts free output
LONG Relay Output12A AC275V Active output
LEGĂTURĂSmartGen special interface for program upgrade, parameter configuration
RS485Modbus-RTU communication protocol, max communication distance is 1000m (HAT361C only)
Standard de proiectareMeet GB/T 14048.11-2016 and IEC/EN 60947-6-1
Cerință de siguranțăMeet EN 61010-1 (installation category (overvoltage type) III, 300V, pollution degree 2), altitude ≤3000m
Dimensiunile carcasei132 mm x 102 mm x 49 mm
Decupaj panou132 mm x 102 mm
Temperatura de lucru(-25~+70)°C
Umiditatea de lucru(20~90)%RH
Temperatura de depozitare(-30~+80)°C
Nivel de protecțiePanoul frontal IP40
Rezistența la izolațieAplicați AC2.2kV voltage între volum maretage terminal și volum scăzuttage terminal and the leakage current is not more than 3mA within 1min; insulation resistor 100MΩ
Greutate0.59 kg

6.2 Compararea modelelor

ArticolHAT361HAT361CHAT363HAT363C
Inputs (L1,N,70V-277V)3+13+13+13+1
Outputs (Fixed + Aux.)4+14+15+15+1
Genset Control
RS485
LONG Output

Note: HAT361/HAT361C defaults to one breaking. HAT363/HAT363C defaults to two breakings.

7. Întreținere

To ensure the longevity and reliable operation of your SmartGen ATS controller, follow these general maintenance guidelines:

  • **Regular Inspection**: Periodically check the controller for any visible damage, loose connections, or signs of overheating.
  • **Cleaning**: Keep the controller's front panel and ventilation openings clean and free of dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • **Actualizări de firmware**: Verificați specificațiile producătorului website for any available firmware updates. Follow the instructions carefully if performing an update.
  • **Environmental Conditions**: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature component failure.
  • **Wiring Integrity**: Annually inspect all wiring connections for tightness and corrosion. Loose connections can lead to intermittent operation or damage.

8. Depanare

If you encounter issues with your HAT361/HAT361C controller, consider the following general troubleshooting steps:

  • **No Power/Display Off**: Check the power supply to the controller. Ensure all power input terminals are correctly wired and receiving the specified voltage.
  • **No Automatic Transfer**: Verify that the controller is in 'Auto Mode'. Check the status of S1 and S2 power sources on the display. Ensure all abnormal conditions (over/under voltage, frequency) are cleared. Review the wiring for S1/S2 voltage inputs and breaker control outputs.
  • **Manual Operation Fails**: Ensure the controller is in 'Manual Mode'. Check the wiring to the S1/S2 close and open outputs.
  • **Alarm Indicator On**: Check the LCD display for specific alarm messages. Refer to the 'Indicator Display' section for common alarm meanings. Address the underlying issue (e.g., voltage abnormality, frequency deviation).
  • **Communication Issues (HAT361C)**: Verify RS485 wiring (A+, B-, GND) is correct and secure. Ensure the 120Ω matching resistor is properly connected if required by your setup. Check communication settings (baud rate, parity) on both the controller and the connected device.
  • **Incorrect Readings**: Confirm that the voltage and current transformer ratios (if applicable) are correctly configured in the controller's settings.

If the problem persists after performing these checks, contact technical support.

9. Sfaturi pentru utilizatori

  • **Parameter Configuration**: Take time to properly configure all parameters, especially voltage and frequency thresholds, to match your specific power system requirements.
  • **Test Regularly**: Periodically test the automatic transfer function to ensure the system operates as expected during a power outage.
  • **Backup Settings**: If possible, record or back up your controller's configuration settings for quick restoration in case of a reset or replacement.
  • **Environmental Protection**: While the front panel is IP40 rated, ensure the overall installation protects the controller from excessive dust and moisture, especially the rear terminals.

10. Garanție și asistență

For warranty information, technical support, or service inquiries, please contact your authorized SmartGen dealer or the manufacturer directly. Keep your purchase receipt and product serial number handy when contacting support.

Informații de contact ale producătorului:

  • Web: www.smartgen.cn/
  • Email: sales@smartgen.cn

SmartGen își rezervă dreptul de a modifica conținutul acestui document fără notificare prealabilă.