Datakom DPR-02

DPR-02 Voltage Protection Controller User Manual

Model: DPR-02

1. Introducere

The Datakom DPR-02 is a three-phase (line to neutral) voltage protection relay engineered to safeguard electrical systems from various voltage anomalies. It provides robust protection against over voltage, sub voltage, and incorrect phase rotation, making it suitable for critical applications in distribution substations, generators, motors, transformers, and compensation systems.

This device offers adjustable over and under voltage limits, along with configurable trip and reset delays, allowing for precise customization to specific system requirements. Both maximum and minimum voltage limits can be set or disabled using trimmers located on the front panel. Corresponding delay times are also adjusted via dedicated trimmers.

Datakom DPR-02 Voltage Protection Controller front view

Figura 1: Față view of the DPR-02 Voltage Protection Controller, showing adjustment knobs and terminals.

2. Caracteristici

  • DIN Rail mounted for easy installation.
  • Adjustable over voltage limit (L-N).
  • Adjustable under voltage limit (L-N).
  • Adjustable TRIP and RESET Delays for precise control.
  • Integrated phase sequence protection.
  • Detection and protection against phase failure.
  • Overvoltagprotecție.
  • Protection against insufficient supply.
  • 6A/277VAC relay output.
  • Suitable for 1-3 phase gasoline and diesel gensets.
  • Designed for front panel mounting.
  • Survives cranking dropouts.
  • Generator protection with built-in alarms and warnings.
Datakom DPR-02 features and operation overview

Figura 2: Pesteview of DPR-02 features and operational principles.

3. Configurare și instalare

The DPR-02 is designed for DIN rail mounting. Proper installation is crucial for reliable operation. Ensure all power is disconnected before proceeding with wiring.

3.1 Conexiuni terminale

The device features clearly labeled terminals for input and output connections:

  • Terminale de intrare: N (Neutral), L1, L2, L3 (Phase voltage intrări).
  • Output Relay Terminals: 1 (NC - Normally Closed), 2 (COM - Common), 3 (NO - Normally Open).

3.2 Schema electrică

Refer to the connection diagram below for typical wiring in a motor protection application. Ensure all connections are secure and comply with local electrical codes.

Datakom DPR-02 Installation Diagram

Figure 3: Typical installation diagram for the DPR-02, showing connections for a 3-phase motor.

Datakom DPR-02 Connection Diagram and Specifications

Figure 4: Detailed connection diagram, LED indicators, and technical specifications.

4. Principii de funcționare

The DPR-02 continuously monitors the line-to-neutral voltages (L-N) and phase sequence to provide comprehensive protection.

4.1 voitage Protection (Under/Over Voltage)

If any phase voltage exceeds the set MAX limit, the "U>" LED illuminates, and the adjusted Delay timer begins to count. If the fault persists beyond the delay, the relay deactivates, the "OUT" LED turns off, and the "U>" LED turns off. Similarly, if any measured voltage drops below the set MIN limit, the "U<" LED illuminates, and the Delay timer starts. If the condition persists, the relay deactivates, and the "OUT" LED turns off, and the "U<" LED turns off.

When the MAX or MIN Voltage trimmer is adjusted to the "OFF" position, the related voltage protection will be disabled.

Toate voltages within adjusted MIN-MAX limits will cause the "U<" and "U>" LEDs to turn off. If the adjusted Reset Delay timer counts to its expiration, the relay output is activated, and the "OUT" LED illuminates.

4.2 Phase Failure Protection

Dacă voltage of any phase falls below 50% of the nominal value, the "U<" LED illuminates, and the relay output immediately deactivates, turning off the "OUT" LED.

4.3 Suprasolicitaretage Protecție

Dacă voltage of any phase goes 50% above the nominal value, the "U>" LED illuminates, and the relay output immediately deactivates, turning off the "OUT" LED.

4.4 Phase Sequence Protection

If the phase sequence is reversed, both "U<" and "U>" LEDs flash, the relay output deactivates, and the "OUT" LED turns off.

4.5 Indicatori LED

The DPR-02 features several LED indicators to provide status feedback:

U<U>ONOUTDescriere
ONONONVoltages OK
ONONSub voltage avertisment
ONSub voltage excursie
ONONPeste voltage avertisment
ONPeste voltage excursie
FLASHONDeclanșare secvență de fază
  • PE: LED de alimentare (verde)
  • OUT: Relay output LED (yellow)
  • U<: Sub voltage Warning LED (red)
  • U>: Peste Voltage Warning LED (red)

5. Întreținere

The DPR-02 is designed for long-term, reliable operation with minimal maintenance. However, periodic checks can help ensure optimal performance:

  • Inspecție vizuală: Periodically inspect the unit for any signs of physical damage, loose connections, or excessive dust accumulation.
  • curatenie: If necessary, gently clean the exterior of the unit with a dry, soft cloth. Do not use liquid cleaners or solvents.
  • Integritatea conexiunii: Ensure all terminal connections remain tight and secure. Loose connections can lead to intermittent operation or damage.

All maintenance should be performed by qualified personnel with power disconnected.

6. Depanare

If the DPR-02 is not functioning as expected, consider the following common issues:

  • Fără alimentare/LED-uri stinse: Verificați volumul de alimentaretage to the N, L1, L2, L3 terminals. Ensure the power source is active and within the specified voltage gama.
  • Unexpected Relay Trip: Verificați dacă volumul măsurattages are within the set MIN/MAX limits. Check for correct phase sequence. Review the delay settings (Trip Delay, Reset Delay) to ensure they are appropriate for the application.
  • Releul nu se activează: Confirmați că volumul de intraretages are stable and within the acceptable operating range. Check the status of the U< and U> LEDs to identify any active voltage defecte.
  • Incorrect Phase Sequence Indication: Double-check the L1, L2, L3 phase connections for correct order.

If issues persist after checking these points, consult a qualified electrician or contact Datakom technical support.

7. Specificații

Detailed technical specifications for the Datakom DPR-02:

ParametruValoare
Oferta nominală Voltage230V-AC (L-N)
Volumul aprovizionăriitage Gama150-300 V-AC (L-N)
Tip de aprovizionareCapacitive, 1-phase
Gama de frecvente47-63Hz
Consumul de energie30VA / 2W (max)
Metoda de măsurareTrue RMS, line to neutral
Voltage Adjustment Accuracy3 %
Precizia repetiției0.5 %
Peste-Voltage Călătoria240-300V-AC (L-N) adjustable
Sub-Voltage Călătoria150-210V-AC (L-N) adjustable
Trip Delay Setup0.5 - 20 sec. adjustable
Reset Delay Setup0.5 - 20 sec. adjustable
Ieșire releu6A @ 277V-AC, 1800VA, 300W
Gama cablurilor terminale2.5 mm² (12AWG)
Screwing Force2.4 Nm (3.6 Lb)
Temperatura de operare-30°C (-22°F) până la 70°C (158°F)
Temperatura de depozitare-40°C (-40°F) până la 80°C (176°F)
Umiditate maximă95% fără condensare
Dimensiuni (LxAxD)36.0 x 90.6 x 58.4 mm (1.42 x 3.57 x 2.30 inchi)
Greutate~90 g (3.17 oz)
InstalareDIN Rail mounted
Materialul carcaseiHigh temp. ABS/PC (UL94-V0)
Protecție IPIP30
Conformity (EU Directives)2006/95/CE (vol. scăzuttage), 2004/108/CE (EMC)
Norms of ReferenceEN 61010 (safety requirements), EN 60255-6, EN 61326 (EMC requirements)